0.2s Class High Precision Cast Epoxy Resin Current Transformer for
energy meter
Theory
A current transformer (CT) is a type of transformer that is used to
measure alternating current (AC). It produces a current in its
secondary which is proportional to the current in its primary.
Current transformers, along with voltage or potential transformers,
are instrument transformers. Instrument transformers scale the
large values of voltage or current to small, standardized values
that are easy to handle for instruments and protective relays. The
instrument transformers isolate measurement or protection circuits
from the high voltage of the primary system. A current transformer
provides a secondary current that is accurately proportional to the
current flowing in its primary. The current transformer presents a
negligible load to the primary circuit.
Applications
Current transformers are the current-sensing units of the power
system. Current transformers are used at generating stations,
electrical substations, and in industrial and commercial electric
power distribution.
Measurement current for Power meter
Measurement current for Energy meter
Measurement current for Protection device
Features
New magnetic material is taken to be the core of the current
transformer, which has high magnetic permeability, low saturation
magnetization and good stability. Therefore, the measuring accuracy
is higher and the instrument security factor is lower. Since the
high quality silicon processed by advanced technology is taken to
be the core of the protection windings, which assured the accuracy
limit factor is higher.
The semicircular ring core and secondary windings are vacuum poured
by high quality epoxide resin in the fire retardant plastic casing,
which has the characteristic of moisture proof, stable performance
and dispensing with maintenance.Small size, light weight, small
footprint, fixed in the ring network switchgear cable.The cable can
cross the current transformer through its internal poles quickly
and uniformly.
The Cast Resin Straight-Through Current Transformer can be divided
several kinds according to the various current ratio, accuracy and
rated loads. The specific parameters are showed in the
corresponding to each model parameter tables.
PARAMETERS
Technical parameters | |
---|---|
Standards | IEC60044-1; IEC 61869-2; ANSI C57.13; NTC 2205; GB1208-2006 |
Rated primary current | 30-1000A |
Rated load | ≤20VA |
Rated frequency | 50Hz or 60Hz |
Rated secondary current | 5A or 1A |
Rated short-time thermal current | 40kA, 1S |
Rated continuous thermal current | 120%I1n |
Secondary winding power-frequency voltage | 3kV, 1min |
Instrument security factor | FS ≤10 |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | φ45xφ120x65 |
Weight (kg) | 2.1 |
Operating conditions | |
Operating temperature | -35°C to +55°C |
Daily average temp | <+40°C |
Altitude | <3500 meters |
Operating conditions - continued | |
Condition | No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current. |
Type | LZCG530-10 | LZCG530-10 | LZCG530-10 | |||||||
---|---|---|---|---|---|---|---|---|---|---|
Purpose | Measuring current transformer | Protection current transformer | Double winding current transformer | |||||||
Rated primary current (AMP) | Accuracy class and rated load(VA) | Accuracy class and rated load(VA) | Composite accuracy class and rated load(VA) | |||||||
0.2S | 0.2 | 0.5 | 10P20 | 10P15 | 10P10 | 0.2S | 0.5 | 10P15 | 10P10 | |
30 | 2 | |||||||||
40 | 2.5 | |||||||||
50 | 3.75 | 2 | ||||||||
75 | 3.75 | 5 | 2 | 3.75 | ||||||
100 | 2.5 | 5 | 7.5 | 2.5 | 3.75 | |||||
150 | 5 | 7.5 | 10 | 2.5 | 3.75 | 6.25 | 2.5 | 3.75 | 2.5 | |
200 | 7.5 | 10 | 15 | 3.75 | 5 | 7.5 | 5 | 7.5 | 3.75 | |
300 | 10 | 15 | 20 | 5 | 7.5 | 10 | 7.5 | 10 | 2.5 | 5 |
400 | 15 | 20 | 25 | 6.25 | 7.5 | 15 | 10 | 12.5 | 3.75 | 5 |
500 | 20 | 25 | 25 | 6.25 | 7.5 | 15 | 15 | 15 | 3.75 | 5 |
600 | 20 | 30 | 30 | 7.5 | 10 | 20 | 15 | 20 | 3.75 | 7.5 |
Model | Primary rated current | Rated load | Aperture (mm) | Description (mm) | Weight (kg) | Material | Water-proof |
---|---|---|---|---|---|---|---|
LZCK-55 | 100-1500A | ≤10VA | φ55 | 180×138×52 | 2 | PC | IP65 |
LMCK185-10 | 300-3000A | ≤25VA | φ185 | 350×283×55 | 4.5 | PC | IP65 |
LZCK310-10 | 300-600A | ≤10VA | φ50 | φ50 x φ110 x 32 | 1 | Resin | silicon case (option) |
LZCK322-10 | 30-600A | ≤10VA | φ50 | φ50 x φ110 x 52 | 1.6 | Resin | silicon case (option) |
LZCK350-10 | 20-600A | ≤25VA | φ50 | φ50 x φ110 x 105 | 3.1 | Resin | silicon case (option) |
LZCG530-10 | 30-600A | ≤20VA | φ45 | φ45 x φ120 x 65 | 2.1 | Resin | silicon case (option) |
P1, P2 is primary polarity terminal, S1, S2 is secondary polarity
terminal.
P2, S2 is homonymous terminals (subtractive polarity).
Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
Beijing GFUVE Instrument Transformer Manufacturer Co., Ltd. was established in 2008. It combined design, manufacturing and sales together as one high-tech enterprise. GFUVE Instrument Transformer company mainly produces less than 35kV current transformer and voltage transformer, split core ct and current clamp models etc.
GFUVE is a leader manufacturer of split core current transformer products in China. It is professional in current transformer, potential transformer and related accessory. The product of outdoor split core current transformer develops very quickly in the global market. Our company has achieved certification to ISO9001. The products are sold to over 30 provinces in China and exported to overseas including South America, Middle East, Southeast Asia, Australia and Africa.
Please contact us now for further business relationship. We are here to provide you the best service and the best product.