Rated voltage 300/500V twin core with bare earth wire PVC insulation Cable according BS 6004 624-Y
APPLICATION
Domestic wiring cable. Can be installed in fxed installations in dry or damp premises clipped to surface, on trays or in free air where the risk of mechanical damage would not be an issue.
Suitable for laying in conduit or trunking where mechanical protection is required.
CONSTRUCTION
Conductor
Copper conductor according to BS EN 60228
(previously BS 6360)
1mm² to 2.5mm²: Class 1 solid conductor
4mm² to 16mm²: Class 2 stranded conductor
Circuit Protection Conductor (Earth)
1mm² to 2.5mm²: Class 1 solid copper conductor
4mm² to 16mm²: Class 2 stranded copper conductor
Insulation
PVC (Polyvinyl Chloride) Type TI1 according to BS EN 50363
Sheath
PVC (Polyvinyl Chloride) Type 6 according to BS 7655
CHARACTERISTICS
Voltage Rating (Uo/U)
300/500V
Temperature Rating
-5°C to +70°C
Short Circuit : +160°C
Minimum Bending Radius
Fixed: 6 x overall diameter
Core Identifcation
Brown Blue
Sheath Colour
Grey
DIMENSIONS
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm² | CONDUCTOR CLASS | CROSS SECTIONAL AREA OF CIRCUIT PROTECTIVE CONDUCTOR mm² | NOMINAL THICKNESS OF INSULATION mm | NOMINAL THICKNESS OF SHEATH mm | NOMINAL OVERALL DIMENSIONS mm | NOMINAL WEIGHT kg/km |
2 2 2 2 2 2 2 3 3 | 1 1.5 2.5 4 6 10 16 1 1.5 | 1 1 1 2 2 2 2 1 1 | 1 1 1.5 1.5 2.5 4* 6* 1 1 | 0.6 0.7 0.8 0.8 0.8 1 1 0,6 0.7 | 0.9 0.9 1 1 1.1 1.2 1.3 0.9 0.9 | 4.35 x 7.95 4.85 x 8.9 5.65 x 10.65 6.3 x 11.95 7.1 x 13.7 8.7 x 17.25 9.85 x 20 4.35 x 9.8 4.85 x 11.2 | 68 87 120 172 235 373 530 91 115 |
CONDUCTORS
Class 1 Solid Conductors for Single Core and Multi-Core Cables
NOMINAL CROSS SECTIONAL AREA mm² | MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC |
Plain Wires ohms/km | |
1 1.5 2.5 | 18.1 12.1 7.41 |
Class 2 Stranded Conductors for Single Core and Multi-Core Cables
NOMINAL CROSS SECTIONAL AREA mm² | MINIMUM NO. OF WIRES IN CONDUCTOR | MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC |
Annealed Copper Conductor | ||
Circular | Plain Wires ohms/km | |
4 6 10 16 | 7 7 7 7 | 4.61 3.08 1.83 1.15 |
ELECTRICAL CHARACTERISTICS
Current Carrying Capacity and Voltage Drop
NOMINAL CROSS SECTIONAL AREA mm² | REFERENCE METHOD A* (IN CONDUIT IN WALL) Amps | REFERENCE METHOD C* (CLIPPED DIRECT) Amps | VOLTAGE DROP mv/A/m |
1 1.5 2.5 4 6 10 16 | 11.5 14.5 20 26 32 44 57 | 16 20 27 37 47 64 85 | 44 29 18 11 7.3 4.4 2.8 |
CN Cable Group Co., Ltd.
ABOUT CN CABLE GROUP
CN Cable Group specializes in the fields of development, design, production, sales, installation and technology service of wires and cables, accessories. We are one of the most experienced manufacturers and suppliers in the global markets.
Our Products mainly include: 500KV and below power cables, bare conductors (AAC, ACSR, ACAR, AAAC, galvanized steel wires, etc.), ABC cables, mining cables, rubber cables, computer cables, telephone cables, control cables, instrument cables, fiber cables, building wires, flat cables, silicon cables, environmental protection cables, cable accessories, etc. The above products had passed the management system certificate of ISO 9001:2015 and ISO 14001:2015 and ISO18001:2007, CE certificate and IEC certificate, etc.
There are large quantities of skilled workers (more than 300 persons) in the factory. Most of them have rich experiences in the field of cable manufacturing, engineering technology, and enterprise management. More than 40 persons are of senior professional and technical personnel, who are the upgraded technology experts and academic technology leaders. Design and production of all of our products are strictly according to the relative standards, GB, IEC, BS, DIN, ASTM, UL, NFC, CSA, and Australian standard, etc. Our products have been exported to more than 100 countries and regions, such as USA, Canada, Brazil, Chile, Peru, South Africa, Tanzania, Kenya, Uganda, Nigeria, Togo, Middle East and Southeast Asia and other countries and regions.
In addition, our professional service team with the fastest speed, best service attitude and best service quality will continue to technical advice, technical guidance, technical training, on-site construction, etc. We will try our best to do well in everything before sales, in sales and after sales with our enthusiasm.
Quality are always the first, must be guaranteed. You are welcome for your witness.