IEC60898 Standard 6KA MCB 1 Pole Red Copper Mini Circuit Breaker
Construction and Feature:
1. Protection against both overload and short circuit
2. Electro-mechanical endurance:4000
3. High short-circuit capacity
4. Easy mounting onto 35mm DIN rail
5. Connection terminal:Pillar terminal with clamp
Electrical Feature | |||
1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63 | |||
Poles | 1P, 2P, 3P, 4P | ||
Rate voltage(V) Ue | 230/400~240/415 | ||
Insulation voltage(V) Ui | 500 | ||
Rated frequency(Hz) | 50 | ||
Tripping curve | B,C,D Type | ||
Standard | IEC60898-1 | ||
Breaking capacity(Ka) | 10 | ||
Power loss per pole | Rated current(A) | Max power loss per pole(W) | |
1, 2, 3, 4, 6, 10 | 2 | ||
16, 20, 25, 32, | 3.5 | ||
40, 50, 63, | 5 | ||
Pollution degree | Ⅱ | ||
Energy limiting class | 3 |
Mechanical Features | |||
Electrical life | 4000 | ||
Mechanical life | 20000 | ||
Contact position indicator | NO | ||
Protection degree | IP20 | ||
Reference temperature for setting of thermal element | 30℃ | ||
Working ambient temperature | -5~40℃ | ||
Storage temperature | -25~70℃ |
Installation | |||
Terminal connection type | Cable | ||
Mounting | On DIN rail IEC60715(35mm) by means of fast clip device |
The maximum permissible crrent in a circuit breaker depends on the
ambient temperature where the circuit breaker is placed. Ambient
termperature is the temperature in side the enclosure or
switchboard in which the circuit breakers are installed.
The reference temperature is 30℃
Rated current(A) | -35℃ | -30℃ | -20℃ | -10℃ | 0℃ | 10℃ |
1 | 1.3 | 1.26 | 1.23 | 1.19 | 1.15 | 1.11 |
2 | 2.6 | 2.52 | 2.46 | 2.38 | 2.28 | 2.2 |
3 | 3.9 | 3.78 | 3.69 | 3.57 | 3.42 | 3.3 |
4 | 5.2 | 5.04 | 4.92 | 4.76 | 4.56 | 4.4 |
6 | 7.8 | 7.56 | 7.38 | 7.14 | 6.86 | 6.6 |
10 | 13.2 | 12.7 | 12.5 | 12 | 11.5 | 11.1 |
16 | 21.12 | 20.48 | 20 | 19.2 | 18.4 | 17.76 |
20 | 26.4 | 25.6 | 25 | 24 | 23 | 22.2 |
25 | 33 | 32 | 31.25 | 30 | 28.75 | 27.75 |
32 | 42.56 | 41.28 | 40 | 38.72 | 37.12 | 35.52 |
40 | 53.2 | 51.2 | 50 | 48 | 46.4 | 44.8 |
50 | 67 | 65.5 | 63 | 60.5 | 58 | 56 |
63 | 83.79 | 81.9 | 80 | 76.86 | 73.71 | 70.56 |
Rated current(A) | 20℃ | 30℃ | 40℃ | 50℃ | 60℃ | 70℃ |
1 | 1.05 | 1 | 0.96 | 0.93 | 0.88 | 0.83 |
2 | 2.08 | 2 | 1.92 | 1.86 | 1.76 | 1.66 |
3 | 3.12 | 3 | 2.88 | 2.79 | 2.64 | 2.49 |
4 | 4.16 | 4 | 3.84 | 3.76 | 3.52 | 3.32 |
6 | 6.24 | 6 | 5.76 | 5.64 | 5.28 | 4.98 |
10 | 10.6 | 10 | 9.6 | 9.3 | 8.9 | 8.4 |
16 | 16.96 | 16 | 15.36 | 14.88 | 14.24 | 13.44 |
20 | 21.2 | 20 | 19.2 | 18.6 | 17.8 | 16.8 |
25 | 26.5 | 25 | 24 | 23.25 | 22.25 | 21 |
32 | 33.92 | 32 | 30.72 | 29.76 | 28.16 | 26.88 |
40 | 42.4 | 40 | 38.4 | 37.2 | 35.6 | 33.6 |
50 | 53 | 50 | 48 | 46.5 | 44 | 41.5 |
63 | 66.78 | 63 | 60.48 | 58.9 | 55.44 | 52.29 |
Zhejiang Sefie Electric Co.,Ltd.
ZHEJIANG SEFIE Electric Co., LTD., Founded in 2011, the specialty is engaged in the export trade, is a professional manufacturer of MCB/MCCB/RCCB and Junction Box/Copper Busbar can be matched.
Provides the Mini Circuit Breaker component complete solution, equipment technical force is abundant, the product range widely, are of High quality and reasonable price, fashionable.
Provide product customization service, products are widely used in the construction industry and other industries.